Top
info@perfectgenerators.com +91 97116 08708

400 kVA / 500 kVA / 625 kVA

Genset Prime Rating (kVA) *400500625
Genset Prime Rating (KW)320400500
Phase / Voltage (V)3/415
Power Factor0.8 (lagging)
Current (A)556695869
Frequency (Hz)& RPM50/1500
Governing classG2 as per
ISO 8528 Part V
G2 as per
ISO 8528 Part V
G2 as per
ISO 8528 Part V
Starting system24 V DC Electrical
Fuel tank capacity (lit)750750900
Genset dimensions w/o silencer (mm) (L x W x H) approx.5000x1900x23605950x2000x2350
Genset Weight (kg) approx.520058007500
Engine Specification
Make / SeriesPerkins
Engine Model2206D-E13TAG32506D-E15TAG22806D-E18TAG 1A
Rated Power at 100% Load @ 1500 RPM (kW)367453540
AspirationTurbo Charged After Cooled
No. of cylinders6
Bore x Stroke (mm)130*157137*171145*183
Displacement (Lit)12.515.218.1
Fuel consumption @ 75% load (lit/hr)^65.578.697
Fuel consumption @ 100% load (lit/hr)^90.5101130
Total lubrication system capacity (lit)406271
Lube oil consumption @ 100% load*0.10% of fuel consumption
Lube oil change period (hrs.)500
Radiator coolant capacity (lit)51.44855.6
Alternator
Enclosure TypeIP23
Voltage regulation±1%
Class of insulationClass H
Maximum Unbalanced Load across Phases25%
CALL US NOW
Mobile: +91 97116 08708
COME VISIT US
Hisali Rd, Mudhiuddinpur Hisauli, Utter Pradesh 201206
SEND US A MESSAGE
info@perfectgenerators.com